Ember-Resistant Garage & Shed Vents: California WUI Code Rules

Updated
In short

Under California's 2025 Wildland-Urban Interface Code, an attached garage is part of the house: in new construction its vents must be State Fire Marshal-listed or tested to ASTM E2886, and gaps around the garage door may not exceed 1/8 inch. A detached garage or shed falls under separate accessory-building rules set by distance (3 and 50 feet) and size (120 square feet). Existing buildings are not ordered to retrofit.

Garage and shed rules at a glance

ASTM E2886 Vent testor an OSFM listing
1/8 inch Max garage-door gapCWUIC 504.9.2
3 ft · 50 ft Distance bands for detachedgarages and sheds

Attached garage: same vent rules as the house

Since January 1, 2026, California's wildfire building rules live in the 2025 California Wildland-Urban Interface Code (CWUIC, Title 24 Part 7). It replaced Chapter 7A of the California Building Code — the OSFM's own WUI Listed Products Handbook says so — and the 2025 California Residential Code keeps only a note under R337 pointing to Part 7. If a contractor or an older article cites "Chapter 7A" or "R337" for garage vents, it is the same subject under its old address.

The code has no separate category for an attached garage. Its vent section, CWUIC 504.10, covers enclosed attics, gable ends, ridge ends, eaves and cornices, enclosed eave soffit spaces, underfloor areas, foundations and crawl spaces — and "any other opening intended to permit ventilation, either in a horizontal or vertical surface." Read as written, a gable vent over the garage, a vent in the garage wall and the attic above the garage are ventilation openings of the same building, so in new construction they follow the same three rules as the rest of the house:

  • Listed or tested vents (504.10.1). Openings must be fully covered with vents approved and listed by the California State Fire Marshal, or with vents tested to ASTM E2886 that show no flaming ignition of the cotton in the ember test, no flaming ignition in the integrity part of the flame test, and no more than 662°F (350°C) on the unexposed side.
  • Mesh only on sloped-roof vents (504.10.2). The 1/16- to 1/8-inch noncombustible, corrosion-resistant mesh path applies to vents installed on a sloped roof, such as dormer vents — not to garage gable or wall vents.
  • Gable vents 10 feet from the lot line (504.10.3). Gable-end and dormer vents must sit at least 10 feet from lot lines. Garages are often the part of a house built closest to a side property line, so this placement rule matters most there.

Your local building official makes the final call on any specific opening; OSFM states in its handbook that the local Authority Having Jurisdiction has the right to approve or disapprove products in its jurisdiction.

The garage door is part of the vent problem

A gap under or around a garage door lets embers in just as a vent does, and the code treats it that way. Section 504.9.2 requires exterior garage doors to resist ember intrusion by keeping gaps between the door and the opening — at the bottom, sides and top — to no more than 1/8 inch (3.2 mm). The code accepts one or more of three methods:

  • weather-stripping whose tensile strength changes by no more than 10 percent after 2,000 hours of ASTM G155 exposure (tested to ASTM D638) and which rates V-2 or better under UL 94;
  • door overlaps onto jambs and headers;
  • garage door jambs and headers covered with metal flashing.

Section 504.9.1 adds that automatic openers for vehicle doors serving a residential building must have a battery backup. That one is also statewide law outside fire zones: under Health and Safety Code 19892, since July 1, 2019 no residential automatic garage door opener without a battery backup may be sold or installed in California, and a replacement garage door may not be connected to an existing opener that lacks one.

Detached garage, shed or workshop: the accessory-building rules

A building that stands on its own is handled differently. CWUIC section 504.11 covers buildings accessory to a home on the same lot, plus permitted miscellaneous structures such as trellises, arbors, patio covers and gazebos, because they "have the potential to pose a significant exterior fire exposure hazard during wildfires." What it requires depends on two numbers: distance from the house and floor area.

Detached buildingWhat the code requires
Any size, less than 3 ft from the house Noncombustible or ignition-resistant materials (504.11.2)
Over 120 sq ft, 3 ft to under 50 ft away Noncombustible or ignition-resistant materials (504.11.3)
120 sq ft or less, 3 ft to under 50 ft away Same materials only where the code official requires it (504.11.4)
Group U, 120 sq ft or less, 50 ft or more away Exempt from the chapter (501.1, Exception 1)

Three details change how this plays out for a garage or shed:

  • The roof. Where an accessory building has to be built of noncombustible or ignition-resistant materials, its roof follows the main roof rules, and in a Fire Hazard Severity Zone it must be a Class A assembly tested to ASTM E108 or UL 790 (504.11.6). Our Class A roof guide covers what that means.
  • Vents are not named. Section 504.11 speaks of materials and roofs; it does not mention vents. New accessory buildings that comply with 504.11 are excepted from the rest of the chapter's construction requirements (503.1, Exception 1). If you are building a regulated shed or detached garage with vent openings, ask the building department whether it expects listed or E2886-tested vents — using them removes the question.
  • A large building 50 feet or more away is not covered by any of the distance bands in 504.11, and the 501.1 exemption is written only for Group U structures of 120 square feet or less (plus Group U agricultural buildings at 50 feet or more). For a big detached garage or workshop at that distance, confirm the requirements with your building official before design, not after.

For context, the code defines an "applicable building" as one with residential, commercial, educational, institutional or similar use, and an "accessory structure" as a building or structure that shelters material, equipment or an occupancy other than a habitable building (CWUIC chapter 2). The distances above are measured from that applicable building on the same lot.

ASTM E2886, OSFM listing and NFPA 1144: what the labels mean

ASTM E2886 is the test named in the code for vents. It has an ember intrusion part and a flame intrusion part, and the code's pass criteria are the three listed above: no flaming ignition of the cotton target, no flaming ignition during the integrity test, and an unexposed-side temperature of no more than 662°F.

An OSFM listing is the State Fire Marshal's Building Materials Listing program publishing a product it has reviewed. Vents are OSFM Category 8165 in the handbook, and you can search current listings at calfire.govmotus.org/BMLSearch. OSFM itself notes that products not listed may still comply with the prescriptive code, "since it is not a statutory mandate to list WUI products with the OSFM." For a garage, the same products serve as for the house: gable, soffit and foundation vents. Our ember-resistant vents guide names the companies holding Category 8165 listings and gives installed costs per vent.

NFPA 1144, the Standard for Reducing Structure Ignition Hazards from Wildland Fire, is another name you may see next to E2886. NFPA's own page says it has been combined into NFPA 1140, with the 2018 edition the last published as a stand-alone standard. It is not the code a California permit is checked against: Part 7 adopts the 2024 International Wildland-Urban Interface Code with California amendments, and that is where the garage, vent and accessory-building sections above come from.

Existing garages and sheds: when it's required and what to do

The construction rules above apply to buildings "hereafter constructed, modified or relocated" into a wildland-urban interface area (CWUIC 503.1), and the code exempts additions to and remodels of buildings originally constructed before July 1, 2008. Which lots count as a WUI area — State Responsibility Area fire hazard zones, locally designated Very High zones and local WUI maps — is covered in the vents guide. In short: an existing garage or shed is not ordered to change its vents. The upgrades below are recommendations.

  • Seal the garage door. CAL FIRE's Low-Cost Retrofit List (updated January 1, 2026) recommends weather-stripping any gap greater than 1/8 inch between garage doors and door frames, using weather-stripping compliant with UL Standard 10C. The code's voluntary Appendix G says the same. (New construction uses the 504.9.2 test criteria above instead.)
  • Replace or screen garage and shed vents. The same CAL FIRE list recommends ember- and flame-resistant vents and says to consult your local building official and hire a licensed contractor, because these modifications may reduce airflow. Appendix G calls 1/16- to 1/8-inch noncombustible, corrosion-resistant mesh over vent openings a temporary solution.
  • Clear around the outbuilding. CAL FIRE's defensible space guidance for Zone 2, out to 100 feet: keep 10 feet of clearance to bare mineral soil around outbuildings and propane tanks, with no flammable vegetation for an additional 10 feet around them. The Low-Cost Retrofit List adds that exposed firewood should be stored at least 30 feet from structures or completely covered in a fire-resistant material, so a woodpile against the shed wall defeats the point. The first five feet around the house itself are the subject of our Zone 0 guide.
  • Going for IBHS designation? The Wildfire Prepared Home technical standard (December 2025) is stricter than the code for outbuildings. At the Base level, sheds, garages and other structures of 15 square feet or more within 30 feet of the home must stand at least 10 feet from it and meet the same requirements as the home — roof, gutters, vents, the 6-inch noncombustible wall base and their own 0–5 ft zone — with no more than three such structures within 30 feet; open detached carports and garages may not store combustible items. At the Plus level, these structures must be at least 30 feet away. See our IBHS guide.

Garage and outbuilding work is usually priced as part of a broader home hardening job — vents, door seals and flashing in one visit. Ask contractors to bid your actual count of vent openings.

Sources checked November 17, 2026.

FAQ

5
Do the vents in an attached garage have to be ember-resistant?

In new construction in a wildland-urban interface area, yes. The 2025 California Wildland-Urban Interface Code (CWUIC, Title 24 Part 7) has no separate category for attached garages; its vent section 504.10 covers attics, gable ends, eaves, soffits, underfloor areas and any other opening intended to permit ventilation, in a horizontal or vertical surface. Those openings must be fully covered with vents listed by the California State Fire Marshal or tested to ASTM E2886. Plain 1/16- to 1/8-inch mesh is the code path only for vents on a sloped roof, such as dormer vents. Your local building official makes the final call on any specific opening.

Does my shed or detached garage need ember-resistant vents?

The code answers this by distance and size, not by vent type. Under CWUIC section 504.11, an accessory building less than 3 feet from the house, of any size, and one larger than 120 square feet within 50 feet of the house, must be built of noncombustible or ignition-resistant materials. A building of 120 square feet or less between 3 and 50 feet away has to meet that only where the code official requires it, and a Group U accessory structure of 120 square feet or less at least 50 feet from the house is exempt from the chapter. Section 504.11 does not itself mention vents, so ask your building official what they expect for vent openings in a regulated outbuilding.

Is NFPA 1144 the vent standard in California?

No. NFPA 1144, the Standard for Reducing Structure Ignition Hazards from Wildland Fire, has been combined into NFPA 1140; NFPA says the 2018 edition of 1144 is the last published as a stand-alone standard. The building rules California permits are checked against are Title 24 Part 7, the 2025 California Wildland-Urban Interface Code, which adopts the 2024 International Wildland-Urban Interface Code with California amendments. For vents, that code names the test: ASTM E2886, or a listing by the State Fire Marshal.

How big a gap is allowed around a garage door?

No more than 1/8 inch at the bottom, sides and top of the door, under CWUIC section 504.9.2 for new construction. The code accepts three ways to control the gap: weather-stripping that passes the code's durability and UL 94 flammability tests, door overlaps onto the jambs and headers, or metal flashing over the jambs and headers. For existing homes, CAL FIRE's Low-Cost Retrofit List recommends weather-stripping any gap greater than 1/8 inch between garage doors and door frames, using weather-stripping compliant with UL Standard 10C.

Do I have to upgrade the vents on an existing garage?

Generally no. The WUI construction rules apply to buildings constructed, modified or relocated into a wildland-urban interface area, and the code expressly exempts additions to and remodels of buildings originally constructed before July 1, 2008. CAL FIRE and the code's own voluntary Appendix G still recommend ember- and flame-resistant vents, with 1/16- to 1/8-inch noncombustible, corrosion-resistant mesh as a temporary solution. One separate state law does reach existing garages at the moment of work: since July 1, 2019, a replacement residential garage door may not be connected to an existing automatic opener that lacks a battery backup.